REGULATION OF 3–PHASE ALTERNATOR BY EMF AND MMF METHODS

EXP.NO. 1                                                                                                                 DATE:

REGULATION OF 3–PHASE ALTERNATOR BY EMF AND MMF METHODS

AIM:
            To predetermine the regulation of 3-phase alternator by EMF and MMF methods and also draw the vector diagrams.

APPARATURS REQUIRED:


SL.NO
Name of the Apparatus
Type
Range
Quantity
1
Ammeter
MC
0 – 1/2 A
1
2
Ammeter
MI
0 – 5/10 A
1
3
Voltmeter
MC
0 – 10 V
1
4
Voltmeter
MI
0 – 600 V
1
5
Rheostat
Wire wound
250 Ω, 1.5 A
1
6
Rheostat
Wire wound
1200Ω, 0.8 A
1
7
Tachometer
Digital
          ---
1
8
TPST knife switch
--
--
1


THEORY:
          The regulation of a 3-phase alternator may be predetermined by conducting the Open Circuit (OC) and the Sort Circuit (SC) tests. The methods employed for determination of regulation are EMF or synchronous impedance method, MMF or Ampere Turns method and the ZPF or Potier triangle method. In this experiment, the EMF and MMF methods are used. The OC and SC graphs are plotted from the two tests. The synchronous impedance is found from the OC test. The regulation is then determined at different power factors by calculations using vector diagrams. The EMF method is also called pessimistic method as the value of regulation obtained is much more than the actual value. The MMF method is also called optimistic method as the value of regulation obtained is much less than the actual value. In the MMF method the armature leakage reactance is treated as an additional armature reaction. In both methods the OC and SC test data are utilized.

PRECAUTIONS:

(i)                 The motor field rheostat should be kept in the minimum resistance position.
(ii)               The alternator field potential divider should be kept in the minimum voltage position.
(iii)             Initially all switches are in open position.

PROCEDURE: (FOR BOTH EMF AND MMF METHODS)

1.     Note down the name plate details of the motor and alternator.
2.     Connections are made as per the circuit diagram.
3.     Switch ON the supply by closing the DPST switch.
4.     Using the Three point starter, start the motor to run at the synchronous speed by adjusting the motor field rheostat.
5.     Conduct Open Circuit test by varying the potential divider for various values of field current and tabulate the corresponding Open Circuit Voltage readings.
6.     Conduct Short Circuit test by closing the TPST switch and adjust the potential divider to set the rated armature current and tabulate the corresponding field current.
7.     The Stator resistance per phase is determined by connecting any one phase stator winding of the alternator as per the circuit diagram using MC voltmeter and ammeter of suitable ranges.

PROCEDURE TO DRAW GRAPH FOR EMF METHOD:
1.      Draw the Open Circuit Characteristic curve (Generated Voltage per phase VS Field current).
2.      Draw the Short Circuit Characteristics curve (Short circuit current VS Field current)
3.      From the graph find the open circuit voltage per phase (E1 (ph) for the rated short circuit current (Isc).
4.     By using respective formulae find the Zs, Xs, Eo and percentage regulation.

PROCEDURE TO DRAW GRAPH FOR MMF METHOD:
1.      Draw the Open Circuit Characteristic curve (Generated Voltage per phase VS Field current).
2.      Draw the Short Circuit Characteristics curve (Short circuit current VS Field current)
3.      Draw the line OL to represent


FORMULAE:
  1. Armature Resistance Ra =        

  1. Synchronous Impedance Zs = O.C. voltage
                                                            S.C. current


  1. Synchronous Reactance Xs = √ Zs2 – Ra2

  1. Open circuit voltage for lagging p.f = √(VcosΦ + IaRa)2 + (VsinΦ + IaXs)2


  1. Open circuit voltage for leading p.f. = √(VcosΦ + IaRa)2 + (VsinΦ – IaXs)2


  1. Open circuit voltage for unity p.f =       √(V + IaRa)2 + ( IaXs)2

  1. Percentage regulation = Eo – V  x 100
                                            V

RESULT:
            Thus the regulation of 3-phase alternator has been predetermined by the EMF and MMF methods.










VIVA QUESTIONS:

  1. What is meant by voltage regulation?

  1. What is meant by Synchronous Impedance?

  1. What is OC test ?

  1. What is SC test?

  1. What is meant by mmf or field ampere turns?






























REGULATION OF 3-PHASE ALTERNATOR BY EMF AND MMF METHODS

TABULAR COLUMNS

OPEN CIRCUIT TEST:



S.No.
Field Current (If)
Open Circuit Line Voltage (VoL)
Open circuit Phase Voltage (Voph)
Amps
Volts
Volts



























SHORT CIRCUIT TEST:



S.No.

Field Current (If)

Short Circuit Current (120% to 150% of rated current) (ISC)
Amps
Amps

















REGULATION OF 3-PHASE ALTERNATOR BY EMF AND MMF METHODS

TABULAR COLUMNS

EMF METHOD:



SL.NO.

Power factor

Eph (V)
% Regulation

Lag

Lead

Lag

Lead




















MMF METHOD:



SL.NO.

P.F

Vph
(V)

If1
(A)

If2
(A)

Ifr
(A)
Eph (V)
% Regulation
Lag
Lead
Lag
Lead
Lag
Lead






























9 comments:

A Beginner’s guide to Electrical Engineering

1. What is Electrical Engineering? Electrical engineering is comparatively one of the newer branches of engineering, and dates b...